Error code: E39

Cause of error code E39

Flue temperature sensor sees temperature higher than 200°F.

Solution for error code E39

1. Read flue gas temperature on user interface. Is temperature higher than 200°F? 
Yes: Boiler is over fired. Wait for the boiler to cool. Fix flow rate problem if any purging all air out of the system. 
No: -> 2


2. Use thermal couple to measure flue gas temperature through sampling port. Is the measured reading on user interface significantly different? 
Yes: Replace flue gas sensor
No: Replace control module. 