Error code:

LOU
List all errors


Error code: LOU

Cause of error code LOU

LOU indicates the 24 volt power supply on the control is damaged or overloaded. This code resets automatically if it is the result of an overload and the overload condition is removed. The second line indicates the status of the pump. Note that while 24 volt power is low, the pump output will be on.

Solution for error code LOU

- Check line voltage. It must be between 100 and 128 volts.
- If available, connect a PC and use Westinghouse service software to check the 24v supply display in the lower left corner of the screen. The number displayed here must be greater than 128 and should be no greater than 250. Use this as a troubleshooting guide as you follow the steps below.
- Remove the 10 pin Molex connector from the customer connection board. If the message clears the problem is with external sensor wiring. Examine the external sensor wiring for shorts to the ground, repairing as necessary. If the message is still present and the boiler is so equipped, disconnect the UL 353 low water cut-off to see if the message clears. Replace the faulty part. Check the low voltage wire harness in boiler for shorts to ground.
- If a message only occurs when the burner tries to light, check the gas valve for excessive current draw.
- If a message is present when the low voltage harness is disconnected from the 926 control board, replace the 926 control board. 